UPS On-line double conversion,
microprocessor-controlled, Power Factor
Corrector input, program of control and
shutdown, Power 1kVA, 2kVA, 3kVA, 6kVA,
10kVA
UPS series ET-6kVA & ET-10kVA possibility
of rendundant parallel, util 3 unit
ET / ETS model (2005) - 220V/230V/240V ON-LINE UPS SPECIFICATION
CAPACITY
VA / W 10000VA/7000W
Vai - Informatics
(Computers data)
15000Vai
INPUT
Voltage Range Base on load percentage (100%-70% / 70%-60% / 60%-50% / 50%-40% / 40%
- 0%)
Line Low Transfer 176 ± 3% Vac
Line Low
Comeback
185 ± 3% Vac
Line High Transfer 276 ± 3% Vac
Line High
Comeback
266 ± 3% Vac
Frequency Range 46Hz ~ 55Hz
Phase Single phase with ground
Power Factor >0.98
OUTPUT
Voltage 220VAC/230VAC/240VAC
Voltage Regulation ± 1%
Frequency (
Synchronized
Range )
46~54Hz
Frequency (
Battery Mode )
50 ± 0.5 Hz
Current Crest
Ratio
3:01
Harmonic
Distortion (linear
Load)
<2% THD
Harmonic Dist.
(non linear Load) <6% THD
Output Waveform Pure Sinewave
EFFICIENCY
To AC Mode >88%
To Battery Mode
>88%
BATTERY
Battery Type 12V/9Ah
Numbers of
Batteries 20
Backup Time,
minutes, PF = 1,0
/ 0,7 / 0,5 RMS
5' / 9' / 15'
Recharge Time 7/8 hours to 90%
Charging Current
(Max.)
2A
Charging
Current, ET(S)
models
4.2A
Charging Voltage 274Vdc ± 0,5%
TRANSFER
TIME
AC to DC
Zero
Inverter to Bypass
Zero
INDICATOR
Status Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault
AUDIBLE
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously Sounding
DIMENSION
Width (mm) 260
Depth (mm) 570
Height (mm) 717
WEIGHT
Net Weight: ET /
ETS 93 kgs /
38kgs
ENVIRONMENT
Operating
Environment 0-40° C
Relative Humidity
20-90% (NON-CONDENSING)
Noise Level @ 1
Meter
<55dB
INTERFACE
Smart RS-232 Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI
IRIX, FreeBSD, HP-UX, and MAC
SNMP (option) Power mana gement from SNMP manager and web browser
|